How Do You Turn Off Emergency Lights in a Building?

4 hours ago
6 min read

Facilities manager in a sky blue shirt turning a small key in a wall-mounted key switch beside a light switch, looking up at a glowing emergency light fitting in a quiet corridor with a closed fire door at the end

TL;DR


  • Most emergency lights are non-maintained: they stay dark while the mains supply is healthy and only light up when it fails. If they are on, the fastest way to turn them off is to find and restore the supply that feeds them.

  • Maintained emergency lights are lit all the time the building is in use. They are switched off with the normal lighting, or by the lighting control system, while the battery stays on charge.

  • The small key switch near a light switch is for testing. Turning it simulates a power cut, so it turns emergency lights on.

  • Never switch off the unswitched supply or unplug a battery to stop a light glowing. The fitting will run its battery down and may not work when you need it.

  • If a light stays on with the power healthy, treat it as a fault and have it checked.


If you have walked into a building after a power cut or late in the evening and found emergency lights still glowing along the corridors, the natural question is how to switch them off. The short answer is that emergency lights are built to stay ready all the time, so there is no normal off switch for the emergency function. What you can do depends on why they are lit, and in almost every case the fix is to restore or check the mains supply that feeds them.


Why are the emergency lights on?


There are three common reasons emergency lights are lit:


  • The mains supply to them has failed or been switched off. Non-maintained fittings light up from their batteries whenever the supply to the local lighting circuit is lost, for example after a power cut, a tripped breaker or an isolated circuit during maintenance.

  • They are maintained fittings. Some emergency lights, often exit signs and lights in theatres, cinemas and public areas, are designed to be lit whenever the building is in use.

  • A key switch has been left in the test position. Turning the test key simulates a mains failure, so the lights stay on until it is turned back.


A fourth, less common reason is a fault, where a fitting stays lit even though the supply is healthy. Our article on why an emergency light won't turn off covers those faults in detail.



How do you turn off emergency lights after a power cut?


When the power comes back, non-maintained emergency lights should go out on their own and start recharging. If they are still lit, the circuit that feeds them has probably not been restored. Check the distribution board for a tripped circuit breaker or RCD and reset it, and check for any isolator or fused spur near the lights that has been switched off. Once the local lighting circuit is live again, the emergency lights should go off. If the breaker will not stay on, there is a fault on the circuit, and our article on why circuit breakers trip and what to do explains what to do next.



How do you turn off maintained emergency lights at night?


Maintained fittings have two supplies: a switched supply that runs the lamp in normal use, and a permanent supply that keeps the battery charged. The switched supply is usually wired to the normal light switch or the lighting control system, so turning the normal lights off when the building closes turns the maintained lamps off too, while the battery keeps charging. If maintained lights in an area stay on all night, check whether that is intended in your fire strategy (many exit signs are meant to stay lit while the building is occupied), and if not, ask an electrician to check how the switched supply is wired.



What does the emergency light key switch do?


The small key switch, often with a slot for a fishtail or T-shaped key, is a test switch. It interrupts the supply to the emergency lights on that circuit so you can see them change over to battery without turning off the general lighting. That is how the monthly functional test, often called a flick test, is carried out. Turning the key turns the emergency lights on. If they are lit and you find the key switch in the test position, turning it back should put them out. Our article on the emergency light flick test explains the routine.



Can you switch off the emergency lighting supply?


Not as a way of stopping a light glowing. If you switch off the permanent supply or disconnect the battery, the fitting will either light up and run its battery flat, or stop working altogether. Either way, it may not light the escape route the next time the power fails. During a refurbishment or decommissioning, an electrician can isolate emergency lighting safely, but only as planned work, with the fire risk assessment reviewed and temporary arrangements in place for anyone still using the area.



What about central battery systems and rest mode?


Some buildings run their emergency lights from a central battery system in a plant room instead of a battery in each fitting. If the lights are lit, check the central panel for a mains failure or fault indication. Some central systems and some self-contained fittings also have a rest mode, which lets a responsible person switch the lit fittings off during a power cut once the building is empty, to save the batteries. It cancels itself when the mains supply returns. Use it only if your system has it and your procedures allow it. Our article on what a central battery fault light means covers the panel indications.



What if an emergency light won't turn off at all?


If a fitting stays lit when the supply is healthy, the key switch is in the normal position and the lights around it have gone out, treat it as a fault. Common causes are a failed charging circuit, a fault in a self-test unit, or a maintained fitting wired as if it were non-maintained. A fitting in that state is running on its battery, which means it may have little or nothing left for a real power cut. Report it, and have it checked during your next round of emergency light testing or sooner.



What to do next: how Protest ES Ltd helps


Emergency lights that come on unexpectedly, or will not go off, are often the first sign that something on the circuit or in the fittings needs attention. We don't simply identify compliance issues. We help clients close them:



One visit, more disciplines. Most FMs use separate contractors for fire doors, fire stopping and electrical testing, each with its own access, programme and paperwork. Protest ES Ltd delivers electrical compliance, fire door work, passive fire protection, including fire stopping and fire compartmentation, on the same visit: one contractor, one programme, one set of records across every site.


If you have emergency lights behaving oddly or want your system tested and recorded, get in touch with our team or visit Protest ES Ltd.



Further reading from Protest ES Ltd




Frequently asked questions


Why are my emergency lights on when the power is on?


Either they are maintained fittings designed to be lit whenever the building is in use, the key switch is in the test position, the local lighting circuit feeding them has tripped, or the fitting has a fault. Check the key switch and the board first, then report the fitting if it stays on.


How do I disconnect an emergency light?


Leave that to an electrician. Disconnecting the permanent supply or the battery stops the fitting from working in a power cut, so it should only be done as planned work, with the fire risk assessment reviewed and cover arranged for the area.


Will emergency lights turn off by themselves?


Non-maintained lights go out by themselves when the mains supply returns, or when their battery runs out after the rated duration, usually one or three hours. A light that goes out because its battery is flat needs time to recharge before it will work again.


Is it safe to leave emergency lights on?


A maintained light that is meant to be lit is fine. A non-maintained light that is lit because of a fault or a lost supply is running on its battery, so it may not have enough charge left for a real emergency. Find the cause and fix it.


What is the key for emergency lights called?


It is usually called a fishtail key or a test key. It operates the key switch that simulates a power cut for the monthly test, and it should be kept with the person responsible for emergency light testing.


How long does it take emergency light batteries to recharge?


Most self-contained fittings take around 24 hours to fully recharge after a full discharge. Avoid a second full duration test in that time, and check the manufacturer's information for your fittings.