Can Fire Doors Be Held Open?

TL;DR
Yes, a fire door can be held open, as long as the device holding it lets the door close by itself when the fire alarm sounds, when a detector picks up smoke, or when the power fails.
Wedges, door stops, hooks, cable ties and closer arms that stay put until someone pushes the door are never acceptable on a fire door.
The usual lawful options are electromagnetic door holders, free-swing closers, hold-open closers and acoustic (sound-activated) units, and each must suit the door and the alarm system.
A held-open fire door should carry an "Automatic fire door keep clear" sign on both faces.
Test every device weekly with the fire alarm test, and have any that fail put right through fire door remedials.
If staff keep wedging a corridor door because it is heavy, slams or gets in the way of trolleys, you are probably being asked whether you can just leave it open. The short answer is yes, provided the door is held by a device that releases it automatically in a fire, and the door then closes fully into its frame on its own. Done properly, that keeps people moving during the day and keeps the fire door working when it matters.
Can fire doors be held open legally?
Yes. Approved Document B, the guidance that supports the Building Regulations, allows a self-closing fire door to be held open where a closer would get in the way of the normal use of the building, provided it is held by an automatic release linked to the fire alarm or by a free-swing closer. The Regulatory Reform (Fire Safety) Order 2005 then requires the responsible person to keep that arrangement in efficient working order, so the device, the closer and the door all have to keep doing their job.
Is it illegal to wedge a fire door open?
Wedging is not named as an offence on its own, but a wedged door stops the fire door working, and that can breach the duty to maintain fire safety measures under the Fire Safety Order. It also undermines your fire risk assessment, which assumes the doors will close. Wedges, fire extinguishers used as stops, hooks and bins are among the commonest findings on a walk round, and our article on why you must prevent fire doors from being wedged open covers the risk in more detail. Treat a repeatedly wedged door as a sign that it needs a proper hold-open device.
Which devices can hold a fire door open?
There are four common types, and each one relies on a signal from the fire alarm, a detector or a sounder to let go:
Electromagnetic door holders: a magnet on the wall or floor, wired to the fire alarm, holds the door until the alarm cuts the power.
Free-swing closers: the door moves freely like an ordinary door during the day and becomes self-closing when the alarm activates.
Hold-open closers: the closer arm holds the door at a set angle and releases it on an alarm signal.
Acoustic units: battery devices that listen for the alarm sound and release the door.
Electrically powered hold-open devices are covered by BS EN 1155 and their link to the alarm by BS 7273-4. Whichever you choose, the closer must still be strong enough to close and latch the door from fully open.
Can any fire door be held open?
No. The door, the building and the alarm system all decide what is suitable. BS 7273-4 groups doors by how critical they are, and doors that protect the only escape stair, or stair doors in buildings where people sleep, need the most dependable release, which usually rules out battery acoustic units. Doors to cupboards, risers and plant rooms should stay locked shut instead. Your fire risk assessor should confirm which doors can be held open and by what, and the answer should be written into the fire door inspection register so the next person knows.
What signs does a held-open fire door need?
A fire door held open by an automatic release or a free-swing closer should carry an "Automatic fire door keep clear" sign on both faces. A "Fire door keep shut" sign on a door that is meant to stand open confuses staff and is a recorded defect. Our article on whether fire doors need signs on both sides explains which sign each door needs and where it goes.
How often should hold-open devices be tested?
Check them every week as part of the fire alarm test: when the alarm sounds, every held door should release and close fully into its frame, latching without help. Note any door that sticks, stops short or bounces off the latch, and get it fixed quickly, because a door that fails here would fail in a fire. Have the devices serviced alongside the fire alarm, and look at them on every fire door inspection.
What usually goes wrong with held-open fire doors?
The same handful of faults turns up on most estates:
A closer too weak to close the door from fully open once the holder lets go, often because it was set for an unheld door.
Door holders fitted to the leaf with screws through the intumescent seal or too close to the edge.
Battery units with flat batteries, or acoustic units that can't hear the sounder after an office layout change.
A trolley, chair or bin parked in the swing, so the released door can't close.
Old "keep shut" signs left on a door that now stands open.
Each of these can be put right with targeted fire door remedials, and our article on how to stop a fire door slamming without making it non-compliant covers the closer side.
What to do next: how Protest ES Ltd helps
Held-open doors are where convenience and compliance meet, and a door that fails to release puts the facilities team's name on the problem. We don't simply identify compliance issues. We help clients close them:
Fire door inspections that check every held-open door releases, closes and latches, and record the device, sign and closer for each one
Fire door remedials to replace wedged doors with suitable hold-open devices, adjust or replace closers, and fit the right signs
Fire door installation of new doorsets with hold-open hardware specified from the start
BM TRADA Q-Mark certification for fire door installation, maintenance and inspection
One visit, more disciplines. Most FMs use separate contractors for fire doors, fire stopping and electrical testing, each with its own access, programme and paperwork. Protest ES Ltd delivers fire door work, passive fire protection, including fire stopping and fire compartmentation, and electrical compliance on the same visit: one contractor, one programme, one set of records across every site.
If your staff keep wedging doors and you want them held open properly, with a record that each one releases, get in touch with our team or visit Protest ES Ltd.
Further reading from Protest ES Ltd
Frequently asked questions
Is it illegal to keep a fire door open?
It is not illegal if the door is held by a suitable automatic device that releases it in a fire. Keeping it open with a wedge or other fixed stop can breach the Fire Safety Order, because the fire door can no longer do its job.
Is it ever acceptable to prop open a fire door?
Only for a moment while someone is actually using the door, such as moving furniture through it with a person standing by. Propping it and walking away is not acceptable. If a door is propped regularly, fit a hold-open device instead.
Can fire doors have a hold-open device?
Yes, most self-closing fire doors can, as long as the device releases on the fire alarm and the door then closes and latches unaided. The exceptions are doors your fire risk assessment says must always be closed, such as cupboard and riser doors, and some critical stair doors where only the most dependable release is suitable.
Are fire doors supposed to be open or closed?
Fire doors should be closed when not in use, unless they are held open by an approved automatic device. Cupboard, store and riser fire doors should be kept locked shut.
Can fire doors be held open during the day?
Yes, with a hold-open device linked to the alarm. Some sites also set magnetic holders to release automatically at night, so the doors close when the building is quiet.
Do magnetic door holders need a fire alarm?
Yes. A mains-powered magnetic holder needs to be wired to the fire alarm so that the alarm, a detector or a power failure cuts the magnet and lets the door close. Where there is no suitable alarm, an acoustic unit or a free-swing closer may be an option, subject to your fire risk assessment.