top of page

Do Fire Doors Need Signs on Both Sides?

1 day ago
6 min read

Facilities manager with a clipboard pointing at the round blue fire safety sign on a closed fire door, in a busy office corridor with a noticeboard, fire extinguisher, plants and three colleagues walking past

TL;DR


  • Most fire doors should be marked with a fire safety sign on both faces, so anyone approaching from either side knows how the door must be used.

  • Fire doors to cupboards and service ducts or risers only need a sign on the outside face.

  • The wording depends on how the door works: "Fire door keep shut", "Fire door keep locked" or "Automatic fire door keep clear".

  • Approved Document B gives a few exceptions, including doors inside flats and houses, hotel bedroom doors and lift entrance doors.

  • Missing, painted over and wrong signs are routine findings on a fire door inspection, and they are among the quickest to put right.


Signs are easy to overlook because they rarely fail on their own. A corridor door gets redecorated and the sign goes back on one face only. A cleaner's cupboard has its sign on the inside where nobody sees it. A door fitted with a hold-open device still says "keep shut", so staff learn to ignore the sign. Each of these is small, but together they tell an auditor how well the doors are managed, and they shape how people treat the door every day.


Do fire doors need signs on both sides?


Yes, in most cases. Approved Document B, the guidance that supports the Building Regulations, says fire doors should be marked with the appropriate fire safety sign, and that all fire doors other than cupboard and service duct doors should be marked on both sides. The reason is simple: people reach a corridor or stair door from both directions, and the instruction needs to be in front of them whichever way they come.



Which fire doors only need a sign on one side?


Doors to cupboards, stores and service ducts or risers only need a sign on the outside face, because nobody uses them from the inside. That covers riser cupboards, electrical and data cupboards, cleaner's stores and meter cupboards. If you are unsure whether one of these doors should be a fire door at all, our article on whether riser cupboard doors need to be fire doors explains how to tell.



Which sign does each fire door need?


The sign follows how the door is meant to behave when it is not in use:


  • "Fire door keep shut" for doors fitted with a self-closing device that should stay closed, which covers most corridor, stair and room doors.

  • "Fire door keep locked" for doors that should be kept locked shut when not in use, such as riser, plant and store cupboards.

  • "Automatic fire door keep clear" for doors held open by an automatic release device linked to the fire alarm, or fitted with a free swing closer, so people know not to block the swing.


All three are blue mandatory signs with white lettering, in the format set out in the UK safety sign standards (BS 5499 and BS EN ISO 7010).



Which fire doors are exempt from signs?


Approved Document B lists a few doors that do not need fire door signs. These are doors inside individual flats and houses, bedroom doors in hotels and other residential buildings, and fire doors at lift entrances. For most commercial estates that leaves very few exempt doors, so the safe starting point is that every fire door on the fire door inspection register needs at least one sign.



Where should the sign go on the door?


Fix the sign at around eye level, roughly central on the leaf, on a flat solid part of the door where it will not be hidden by an open leaf, a vision panel frame or a noticeboard. Avoid fixing signs over the intumescent seals, onto glazing beads or across a vision panel. On a pair of doors, a sign on each leaf makes it clear that both leaves are part of the fire door, so neither is mistaken for an ordinary door.



What signage faults turn up most often?


The same handful of faults appears on most walk rounds:


  • A sign on the corridor face only, usually after redecoration or a door replacement.

  • Signs painted over, faded or peeling, or replaced with a handwritten note.

  • "Keep shut" on a door now held open by a hold-open device, which should say "Automatic fire door keep clear".

  • A cupboard or riser door signed on the inside, or not at all.

  • A "Fire door" sign left on a door that is no longer a fire door after a refurbishment, which confuses the register.


None of these needs specialist kit, but each one is a recorded defect, and a fire risk assessment will usually pick them up alongside the issues covered in our article on what happens if a fire door fails an inspection.



Does a sign make a door a fire door?


No. A sign only tells people how to use the door. A fire door is a tested and certified doorset, identified by its label or plug, its frame, seals, hinges and closer working together. A sign on an ordinary door gives false confidence, and a missing sign on a real fire door does not reduce its fire resistance. Our article on how to know if a door is a fire door covers how to check.



Who is responsible for fire door signs?


The responsible person under the Regulatory Reform (Fire Safety) Order 2005, usually the employer, owner or the organisation managing the building, is responsible for keeping fire safety measures in efficient working order, and that includes signs. In practice the facilities team owns the task. Recording signage on every fire door inspection gives you evidence it was checked, door by door, as explained in our article on who is responsible for fire door inspections in a commercial building.



What to do next: how Protest ES Ltd helps


Protest ES Ltd works with facilities managers, managing agents and FM providers across commercial, education, healthcare and public sector estates. We don't simply identify compliance issues. We help clients close them:



One visit, more disciplines. Most FMs use separate contractors for fire doors, fire stopping and electrical testing, each with its own access, programme and paperwork. Protest ES Ltd delivers fire door work, passive fire protection, including fire stopping and fire compartmentation, and electrical compliance on the same visit: one contractor, one programme, one set of records across every site.


If your doors have missing or mixed signs and you want a clear record of every door before your next audit, get in touch with our team or visit Protest ES Ltd.



Further reading from Protest ES Ltd




Frequently asked questions


Do fire door keep shut signs have to be blue?


Yes. "Fire door keep shut" is a mandatory instruction, and mandatory safety signs in the UK use white symbols and lettering on a blue background. Photoluminescent versions are available for darker areas, and they follow the same blue format.


Is it a legal requirement to have fire door signs?


The Health and Safety (Safety Signs and Signals) Regulations 1996 require safety signs where a risk cannot be controlled another way, and the Regulatory Reform (Fire Safety) Order 2005 requires fire safety measures to be maintained. Approved Document B then sets out which fire doors should be signed and on which faces. Your fire risk assessor will expect to see signs that match.


Do fire exit doors need a "Fire door keep shut" sign?


A final exit door to the outside usually carries a green fire exit sign, plus a "Push bar to open" or similar sign for its hardware. If the same door is also a fire door separating parts of the building, it should carry the fire door sign that matches how it works as well.


Do double fire doors need a sign on each leaf?


Signing each leaf on each face is good practice, because it shows that both leaves form part of the fire door. If only one leaf is signed, the other can be treated as an ordinary door and wedged or propped open.


Do fire doors with hold-open devices need a different sign?


Yes. A door held open by a device that releases when the fire alarm sounds should carry an "Automatic fire door keep clear" sign on both faces, so people know not to put anything in its swing. A "keep shut" sign on that door contradicts how it is meant to work.


Can I use stickers for fire door signs?


Self-adhesive signs are widely used and acceptable, as long as they are the correct mandatory sign, stay firmly fixed and are not stuck over seals, glazing beads or the door's certification label. Check them during routine walk rounds, because cleaning and redecoration often lift or cover them.