How to Stop Fire Door Defects Coming Back in 2027

TL;DR
Repeat fire door defects usually have a cause that the last repair did not touch: a closer that is too weak for the door, a door that sits in the way of a busy route, or redecoration that paints over the seals.
For each defect that has come back, record why it came back and fix that as well as the door.
Set your 2027 check frequency by how hard each door works, using your fire risk assessment, and check the busiest doors more often.
Brief decorators, cleaners and other contractors on what they must not do to a fire door, and check their work before you sign it off.
Keep a door by door record of defect, cause, repair and recheck, so an auditor can see each fault closed and staying closed.
If your last inspection report reads a lot like the one before it, with the same closers drifting, the same seals painted over and the same doors found wedged open, you are probably planning 2027 with one question in mind: how do you make the repairs last? The answer is to treat each repeat defect as a symptom, find what keeps causing it, and change that alongside the repair. Then check the doors that work hardest more often, and keep records that show the fault stayed fixed.
How do you stop fire door defects coming back in 2027?
Start with last year's inspection reports and pick out every defect that has appeared more than once on the same door or in the same area. For each one, ask what made it happen, then plan the fix for the cause as well as the door. Book fire door remedials to put the door right, change whatever caused the fault, and recheck the door a few months later to confirm it held. Doing this for your top ten repeat defects will usually clear most of the repeat findings on next year's report.
Why do the same fire door defects keep coming back?
Fire doors fail in use far more often than they fail on their own, so a defect that returns is usually telling you something about how the door is used or looked after. The common causes are:
The door is in the way. Staff wedge or prop doors on busy routes, near kitchens or outside meeting rooms because the door slows them down.
The closer does not suit the door. A closer set too weak or too strong, or one that is too small for a heavy or wide leaf, drifts out of adjustment or gets disconnected by frustrated users.
The door takes knocks. Trolleys, cleaning machines and deliveries damage the leaf, edges and frame, which opens up gaps and loosens hinges.
Other trades work on it. Decorators paint over intumescent strips and smoke seals, and installers drill holes for access control or cabling without restoring the door.
Repairs treat the symptom. Re-tightening a closer or hinge without finding out why it loosened means the fault returns at the next check.
Knowing which of these applies to each door tells you what to change in 2027.
Which recurring defects should be on your 2027 plan?
These are the repeat defects most FMs will recognise from their own reports, each with the change that stops it coming back:
Doors wedged or propped open. If a door has a real reason to stand open, consider a hold-open device linked to the fire alarm, so it closes when the alarm sounds. Our article on why you must prevent fire doors from being wedged open explains the risk.
Closers that drift or have been disconnected. Check the closer suits the leaf size and weight, then set it so the door closes fully onto the latch from any angle without slamming. Our article on how to stop a fire door slamming without making it non-compliant covers the adjustment.
Painted or missing seals. Replace damaged intumescent strips and smoke seals, then add a line to every decorating brief that seals must be masked and never painted. See our article on whether you can paint a fire door.
Gaps that keep opening up. Gaps around the leaf usually follow loose or worn hinges, a dropped leaf or a damaged frame. Fix the hinges and frame first, then the gap, as explained in our article on the maximum gap allowed under a fire door.
Impact damage on the lower leaf. Where trolleys hit the same doors, a suitable kick plate protects the leaf. Our article on whether you can put a kick plate on a fire door explains what to check first.
Unsealed holes from cabling or access control. Make sure any contractor who works on a fire door reports it, and that every hole is properly made good before they leave.
What should you change in 2027 so repairs last?
Most repeat defects stop once a few working habits change. Add these to your 2027 plan:
Brief every contractor. Decorators, cleaners, security installers and IT contractors should know that fire doors are not to be painted over, drilled, wedged or modified without approval.
Sign off work on fire doors. When another trade has worked on or near a fire door, check the door before you sign their work off, while they are still on site.
Tell staff why. A short note to building users on why fire doors must close, and who to report a faulty door to, reduces wedging and gets faults reported sooner.
Repair with matching parts. Hinges, closers, seals and other hardware should be suitable for the fire door and compatible with its certification. Our article on whether a fire door can be repaired or needs replacing explains where the line sits.
Recheck the doors you fixed. A quick look at repaired doors two or three months later shows whether the fix held before the next full inspection.
How often should you check fire doors in 2027?
There is no single interval set in law for every commercial building. Your fire risk assessment and the way each door is used should set the frequency, with your busiest doors checked most often. Many FMs pair a documented fire door inspection at least once a year with simple walk round checks of high traffic doors between visits. In residential buildings over 11 metres with common parts, the Fire Safety (England) Regulations 2022 require quarterly checks of communal fire doors and annual checks of flat entrance doors, on a best endeavours basis. Our article on how often fire doors should be checked in a school or hospital looks at higher risk settings.
What records show your defects are closed?
An auditor or insurer wants to see that a defect was found, fixed and stayed fixed. For each door, keep:
the defect found, with a photo and the date
the likely cause, so the pattern is visible across the estate
the repair carried out, by whom, with parts used and an after photo
the recheck date and result
Kept this way, your records show a falling number of repeat defects through 2027, which is strong evidence that the doors are being actively managed. Our article on how to prove fire doors are compliant to an auditor covers what to hand over, and our article on what a fire door remedial report should include sets out the detail to ask your contractor for.
Does the law on fire doors change in 2027?
This plan does not rely on any change in the law. It works from the existing duty in Article 17 of the Regulatory Reform (Fire Safety) Order 2005, which requires the responsible person to keep fire safety measures, including fire doors, maintained in an efficient state, in efficient working order and in good repair. If guidance or standards change during the year, check gov.uk and ask your fire risk assessor before you change your programme. For the priorities we set out for this year, see our earlier article on building a fire door strategy for 2026.
What to do next: how Protest ES Ltd helps
Seeing the same defects on every report is frustrating, and it can suggest to an auditor that the doors are not under control, even when your team is working hard on them. Protest ES Ltd works with facilities managers, managing agents and FM providers across commercial, education, healthcare and public sector estates. We don't simply identify compliance issues. We help clients close them:
Fire door remedials that fix the door and the cause behind the defect, with before and after photos for every door
Fire door inspections that record defects door by door and show which ones are repeats
Fire door installation where a door is beyond repair or no longer suits how the space is used
BM TRADA Q-Mark certification for fire door installation, maintenance and inspection
One visit, more disciplines. Most FMs use separate contractors for fire doors, fire stopping and electrical testing, each with its own access, programme and paperwork. Protest ES Ltd delivers fire door work, passive fire protection, including fire stopping and fire compartmentation, and electrical compliance on the same visit: one contractor, one programme, one set of records across every site.
If you want 2027 to be the year your repeat fire door defects come off the report, get in touch with our team or visit Protest ES Ltd.
Further reading from Protest ES Ltd
Frequently asked questions
What are the most common fire door defects?
The defects found most often are doors wedged or propped open, closers that do not shut the door fully onto the latch, damaged or painted intumescent strips and smoke seals, excessive gaps around the leaf, loose or missing hinge screws and impact damage to the leaf or frame. Most of them are caused by daily use, which is why they tend to come back unless the cause is dealt with.
Who is responsible for keeping fire doors in good repair?
The responsible person under the Regulatory Reform (Fire Safety) Order 2005, usually the employer, owner or the organisation managing the building, must keep fire doors maintained and in good repair. In practice the facilities team arranges the checks and repairs and keeps the records.
Can a facilities team fix fire door defects themselves?
Simple checks, such as confirming a door closes onto its latch and that nothing is wedging it, can be done by the site team. Repairs to the leaf, frame, seals, hinges or closer should be carried out by a competent person using parts compatible with the door's certification, so that the door keeps its fire performance.
How quickly should a fire door defect be repaired?
As soon as is reasonably practicable, with the most serious defects first. A door that will not close or has a large gap should be dealt with straight away, while minor defects can be grouped into a planned programme. Your fire risk assessor can help set the priority for each finding.
Do fire door hold-open devices stop doors being wedged?
They often do, because they give staff a safe way to keep a busy door open. The device must release the door when the fire alarm sounds, and it should be included in your routine testing so you know it still works.
Should repeat defects be recorded differently?
It helps to flag them. Marking a defect as a repeat on the door's record shows where the cause has not been dealt with, and it lets you show an auditor how the number of repeats falls once changes are made.












.png)